Specification Details For ANTSPACE HK3
Product Overview | |
Version | ANTSPACE HK3 |
Dimensions (l*w*h) (mm) | 6058*2438*2896 |
Miner capacity | 210 units -S19 Hyd. Series miner |
Container certification | China Classification Society Certification |
Safety certification | North America/Standards:NFPA 79:2021,UL 508A:2018 R8.21, CSA C22.2 No. 14-18,ANSI/ISO 12100:2012 EU/Standards:EN ISO 12100,EN 60204-1 |
Operating power(kW) | 1047~1050 |
PUE(Power usage effectiveness) | 1.022(Excluding cooling tower)/1.036(Including cooling tower) |
Input voltage and frequency | 415V±5% 60Hz(North America) 400V±5% 50Hz(EU、Middle East) |
Detailed Characteristics | |
Shipping weight(T) | 8 |
Operating weight (T) | 12 |
Main switch of power distribution cabinets(A) | 1200(North America) 1250(EU、Middle East) |
Rated current(A) | 952 |
Standard power(kW) | 1049 |
Maximum power(kW) | 1050 |
Rated current per Miner(A) | 10 |
Inlet cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase: L1 single core cable 600kcMil(300mm²)x4 L2 single core cable 600kcMil(300mm²)x4 L3 single core cable 600kcMil(300mm²)x4 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2 |
Connection interface(Cooling tower) | DN125(GB/T 9119-2010 PN16 DN125) |
Connection interface(Plate heat exchage interface) | DN100(GB/T 9119-2010 PN16 DN100) |
Flow rate(m³/h) | >85 |
Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 |
Specification Details For Plate Heat Exchanger
Product Overview
Type | Plate Heat Exchanger |
Dimensions(L*W*H)(mm) | 775*480*1069 |
Material | TI |
Detailed Characteristics
Shipping Weight(KG) | 379 |
Operating Weight(KG) | 461 |
Connection Interface | DN100(GB/T 9122-2010 PN16 DN100) |
External circulation supply liquid temperature (℃) | 0~30 |
External circulation flow rate (m³/h) | 33~110 |
Internal circulation flow rate (m³/h) | 100 |
| Points For Attention
1 | Cooling tower is required to be placed on flat ground, horizontal degree (±1 degree). |
2 | The ground surfaced is required to be hardened and stable, able to withstand at least 14-ton load. |
3 | A 10-ton crane is needed for unloading ANTSPACE and cooling tower. |
4 | Add-on items such as stairs, transformers, cables, bridge racks and cable distribution boxes are not included in the delivery of ANTSPACE. BITMAIN team can provide design suggestions if needed. |
5 | Client needs to confirm the opening directon of container and it needs to face air-intake. Door on left is current design by defult. |
6 | Keep at least 2 meters of air in-take space around the cooling tower. |
7 | Altitude: ≤3000m. If the altitude is higher than 1000-meter, transformer and switch should be derated, the total power of ANTSPACE must be decreased by 1% for each elevation increment of 100 meters. |
8 | Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. When the initial coolant temperature is below 20 °C, the internal circulation should be turned on to heat up the coolant to above 20 °C before starting the mining machine. |
9 | When the ambient temperature is below 5 ℃, the cooling tower can be switched to cold-dry mode. |
10 | Choose pure water or suitable antifreeze as coolant based on local climate conditions. |
11 | The suitable ambient temperature for ANTSPACE does not represent the suitable ambient temperature for mining machine. |